Description
- Stainless Steel Fire Tube Heat Exchanger with non-metallic base
- Floor Standing or Wall Mount Boiler (optional wall mount kit for 220-399 sizes)
- Available in 5 Sizes: 110, 155, 220, 299, 399 MBH
- Modulating Condensing Boiler
- 95% AFUE (110-299); 96.5% Combustion Efficiency (399)
- 4 Pump/Auxiliary Outputs (Example: 1 boiler loop pump +3 zone pumps)
- Up to 8 Multiple Boiler Control with lead/lag rotation
- Modbus® to BMS connectivity
- Each input can be assigned to a priority (Up to 3 Priorities)
- Multiple Inputs can be assigned one priority (Zone Based Control)
- All Lag Boiler Inputs and Output can be used
- 0-10 Volt Input (modulation or set point)
- Configurable Auxiliary Input/Output System
- Boiler Circulator Included (ECM version with 110-155)
Technical Data
Models | AFUE (%) | CSA Input (MBH) | Net (MBH) | DOE Heating Cap. (MBH) | Vent Size (in.) |
---|---|---|---|---|---|
EVG-110 | 95 | 110 | 88 | 101 | 3 |
EVG-155 | 95.1 | 155 | 124 | 143 | 3 |
EVG-220 | 95 | 220 | 179 | 206 | 3 or 4 |
EVG-299 | 95 | 299 | 243 | 280 | 4 |
EVG-399 | 96.5* | 399 | 333 | 383* | 4 |
Product Video
Downloads
Technical Documents
Evergreen Pro Easy Up Manifold Submittal 0121
Evergreen WM97+ ECO_Direct Exhaust Venting Kit Instructions 1018_1
EVG 220-399 Direct Exhaust Venting Kit Instructions 10-2017_0
Evergreen Pro Sizes 220-399 Vent Category II Boiler Manual Addendum 1220 Web Version
Weil-McLain_Evergreen_299-399_SeismicAnalysis-1008-1065-009
Weil-McLain_Evergreen_220_SeismicAnalysis-1008-1065-400
Evergreen 220-299-300-399 Boilers specs -Fr
Evergreen Pro Suggested Specifications 110-399 0221_0
PP EVG UG WM97+ ECO AB SF Gas Boilers_1
ProtoNode Complete Point List Supplement – JAN19_0
Protonode_StartUpGuide_LongVersion
Brochures and Sales Collateral
Top Reasons Why To Buy Evergreen Pro Sales Flyer 0121
Evergreen Pro Easy Up Manifold Kits 0121
Evergreen Pro 220-339 Brochure 0121
Evergreen Pro 110-399 Brochure 0321
Case Studies
Saucon Valley Country Club – Weyhill Guest House Case Study
Belmont Harbor Condominiums Case Study
Drawings
Manuals
EVG 220-399 Addendum Direct Exhaust Venting 10-2017
Evergreen Pro Sizes 220-399 Advanced Manual 1220 Web Version
Evergreen Pro Sizes 110-155 Advanced Manual 1220 Web Version
Evergreen Pro Sizes 220-399 Users Manual 1220 Web Version
Evergreen Pro Sizes 110-155 Users Manual 1220 Web Version_0
Supplements
Evergreen Pro Modbus Supplement 1220 Web Version
Warranty Information
Evergreen Pro Boiler Warranty – Residential Applications – 110-399 550141109 – 0221 with CP Numbers
Evergreen Pro Boiler Warranty – Commercial Applications – 110-399 550141110 – 0221 with CP NumbersF
Reviews
There are no reviews yet.